Molded Case Circuit Breaker EB2 125/4H 50A 4p 004672109
Specifications
- ETI Code:
- 004672109
- Description:
- EB2 125/4H 50A 4p
- Class name:
- Molded Case Circuit Breaker
- Catalogue Group:
- EB2
- Rated current (A):
- 50
- Number of poles:
- 4
- Connection type:
- front connection
- Rated impulse withstand voltage Uimp (kV):
- 8
- Rated short-circuit breaking capacity at 415V Icu/Ics (kA):
- 65/36
- Rated operational voltage AC (V):
- 690V
- Rated operational voltage DC (V):
- 250V
- Rated insulation voltage (V):
- 800
- Thermal adjustment:
- 0,63-1
- Magnetic adjustment:
- 6-12
- Adjustable or fixed:
- adjustable
- Standards:
- 60947
Documents
Logistic Data
Product
- Customs tariff
- 85362010
- logis_net_width
- 120 mm
- logis_net_height
- 165 mm
- logis_net_depth
- 92 mm
Transport packaging
- Transport packaging quantity
- 1
- EAN code for a transport packaging
- 3838895664628
- Transport packaging weight
- 1.4 kg
- Pallet quantity
- 571
ETIM Clasification
- Classification
- EC000228
- Class name
- Power circuit-breaker for trafo/generator/installation protection
- Rated permanent current Iu
- 50A
- Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
- 65/36kA
- Overload release current setting
- 31.5…50A
- Adjustment range undelayed short-circuit release
- 300…600A
- Type of electrical connection of main circuit
- Screw connection
- Device construction
- Built-in device fixed built-in technique
- With switched-off indicator
- Yes
- Number of poles
- 4
- Type of control element
- Rocker
- Motor drive integrated
- No
- Motor drive optional
- Yes
- Degree of protection (IP)
- IP20
Images & Diagrams
Software & drivers

Tags
Accessories 69
>
>